Siemens 5SV3646-6KL — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV3646-6KL RCCB, 63 A, 4-pole, Type A, 10 kA

MPN5SV3646-6KL
Active

Siemens SENTRON 5SV3646-6KL, 4-pole RCCB, 63 A, Type A, 10 kA SCCR, 230/400 V, DIN rail mount, instantaneous.

$235.43Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV3646-6KL — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII
5SV3646-6KL — Identification
ParameterValue
Product designationRCCB
Product design / constructionInstantaneous
5SV3646-6KL — Mechanical
ParameterValue
Mounting positionany
Maximum45 °C
Minimum-25 °C
Width72 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SV3646-6KL — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

63 A, 4-pole, Type A — panel fit

The Siemens 5SV3646-6KL is a 4-pole residual current circuit breaker (RCCB) rated 63 A at 230/400 V AC, with a 10 kA short-circuit current rating.

At 65 °C it derates to 57.35 A, and at 70 °C to 48.84 A. The I²t let-through is rated 110 000 A²s, and surge current resistance is 1 kA — both figures govern coordination with upstream MCBs or fuses during fault events.

Mounts on DIN rail (REG) in any position — top or bottom feed. Depth is 70 mm, height 90 mm, width 72 mm (4 width units). IP20 with conductors connected and the distribution board installed; finger and back-of-hand safe per the protection class. Neutral is on the left (N left variant). The minimum test voltage is 100 V. Overvoltage category III, suitable for fixed-installation distribution boards.

Frequently asked questions

What is the difference between Type A and Type B RCCB?

Type A (this part) detects sinusoidal AC and pulsating DC fault currents. Type B additionally detects smooth DC fault currents up to the rated residual current — needed for drives, UPS, and PV inverter circuits where pure DC faults can occur.

Does the 5SV3646-6KL require neutral on the left?

Yes, this variant has neutral on the left (N left). Confirm the busbar and wiring layout in your distribution board matches before ordering.