The Siemens 5SV3647-4 is a 4-pole Type B RCCB rated at 80 A and 300 mA sensitivity for 400 V AC systems. The short-time delayed design allows it to ride through transient inrush without tripping.
Mounting and integration — fits standard SENTRON panels
DIN rail (REG) fastening, 60 mm grid spacing, and any mounting position. The 70 mm installation depth matches the standard SENTRON enclosure depth, so no panel rework is needed when swapping in or adding this RCCB to an existing distribution board. IP20 protection applies only when the distribution board is installed and conductors are connected — treat it as a panel-internal device, not for wet or outdoor locations.