Skip to main content
Siemens 5SV3647-4KK14 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV3647-4KK14 SENTRON RCCB, 4P, 80 A, 300 mA, Type B

MPN5SV3647-4KK14
Active

Siemens SENTRON RCCB, 4-pole, 80 A, 300 mA residual, Type B+, short-time delayed, 10 kA SCCR, 4 MW, DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV3647-4KK14 — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII
5SV3647-4KK14 — Identification
ParameterValue
Product designationRCCB
Product design / constructionShort-time delayed
5SV3647-4KK14 — Mechanical
ParameterValue
Mounting positionany
Width in modular units4
Maximum45 °C
Minimum-25 °C
Width72 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SV3647-4KK14 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

Type B+ means it catches smooth DC fault currents up to 6 mA plus the full AC/DC spectrum — essential on VFD-fed circuits, UPS outputs, or EV charging stations where standard AC types would miss a DC fault. Rated 80 A flat from 40 °C through 55 °C, then derates linearly: 72 A at 55 °C, 64 A at 60 °C, 56 A at 65 °C, 48 A at 70 °C. That thermal curve means you don't lose headroom in a warm panel until you're past 50 °C — typical for a ventilated enclosure. Depth is 70 mm — fits standard 100 mm deep enclosures without crowding the gland plate.

Selectivity and coordination

The short-time delayed design (S-type) gives you selectivity with downstream MCBs or RCCBs — the 5SV3647-4KK14 holds through transient inrush and lets the closer device clear a bolted fault first. Rated short-circuit current withstand is 10 kA per IEC 61008-1, with a let-through current permissible of 7,000 A and an I²t value of 60,000 A²·s.

Installation notes

Test circuit minimum supply voltage is 70 V AC. Operating frequency is 50/60 Hz, supply voltage range 70–440 V AC. Silicon-free construction (no silicone outgassing) — relevant for clean-room or paint-shop panels where contamination is a risk.

Frequently asked questions

What is the 5SV3647-4KK14's rated residual current and type?

300 mA, Type B+ — catches smooth DC fault currents plus the full AC/DC spectrum, making it suitable for VFD, UPS, and EV charging circuits.

What is the thermal derating for the 5SV3647-4KK14?

Rated 80 A from 40 °C through 50 °C, then derates to 72 A at 55 °C, 64 A at 60 °C, 56 A at 65 °C, and 48 A at 70 °C.

Where can I buy the 5SV3647-4KK14?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or price is published here.

MPN
5SV3647-4KK14