It's an instantaneous (non-time-delayed) Type A device, meaning it detects sinusoidal AC residual currents plus pulsating DC residual currents up to 300 mA — the trip threshold. The 10 kA short-circuit current rating tells you it can withstand a fault up to that level without rupturing, provided the upstream protective device limits let-through energy to the listed 58 000 A²·s and peak current to 5 200 A. Rated supply voltage is 500 V AC at 50 Hz.
Depth is 70 mm, installation depth the same. Supply can enter from top or bottom. IP20 rating applies once installed in a distribution board with conductors connected. Overvoltage category III.
The 5SV3652-6 carries a current lifecycle status. Silicon-free construction is noted for applications sensitive to silicone outgassing.