Skip to main content
Siemens 5SV3746-6 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV3746-6 SENTRON RCCB, 4P, 63 A, 500 mA, 400 V AC

MPN5SV3746-6
Active

Siemens SENTRON 5SV3746-6, 4-pole RCCB, type A, In 63 A, 500 mA, Un AC 400 V, 10 kA SCCR, IP20, DIN-rail mount.

$140.64Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SV3746-6 — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII
5SV3746-6 — Identification
ParameterValue
Product designationRCCB
Product design / constructionInstantaneous
5SV3746-6 — Mechanical
ParameterValue
Mounting positionany
Width in modular units4
Maximum45 °C
Minimum-25 °C
Width72 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SV3746-6 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

The Siemens SENTRON 5SV3746-6 is a 4-pole residual current circuit breaker (RCCB), type A, rated 63 A with a 500 mA trip sensitivity and 400 V AC supply voltage. It carries a 10 kA short-circuit current rating and is designed for instantaneous operation — no intentional delay, so it responds to earth faults without coordination lag.

The 500 mA residual sensitivity is on the higher side — suited for circuits with natural leakage (long cable runs, industrial heaters) where a 30 mA device would nuisance-trip. The 10 kA SCCR is the withstand rating under IEC 61008-1; the rated conditional short-circuit current is 0.8 kA per that standard. The maximum permissible series fuse is 100 A — upstream protection must be coordinated to that level.

Occupies 4 modular width units at 60 mm grid spacing — 72 mm wide, 70 mm deep, 90 mm tall. Mounts on DIN rail (REG) in any position. IP20 with the distribution board installed and conductors connected; overvoltage category III. Silicon-free construction, which matters for coating-sensitive environments like automotive paint lines or semiconductor fab sub-panels. Supply connection can be top or bottom.

Frequently asked questions

What is the closest functional alternative — the 5SL4363-7?

The 5SL4363-7 is a miniature circuit breaker (MCB), not an RCCB. It has 3 poles, 54 mm width, and a 10 kA SCCR, but it lacks residual current detection. The 5SV3746-6 is the correct part for earth-fault protection; the 5SL4363-7 is a different device class and cannot substitute.

What is the depth of the 5SV3746-6?

70 mm installation depth, matching the overall depth dimension.

What is the width of the 5SV3746-6?

72 mm, which corresponds to 4 modular width units on a 60 mm grid.

Will the 5SV3746-6 drop into a panel designed for the 5SL4363-7?

No. The 5SL4363-7 is a 3-pole MCB at 54 mm wide (3 MW); the 5SV3746-6 is a 4-pole RCCB at 72 mm wide (4 MW). The footprint, function, and wiring scheme are different — panel rework is required.