Siemens 5SV4317-0KL — Residual Current Breakers (RCCB/RCBO)

Siemens SENTRON 5SV4317-0KL RCCB, 2P, 80 A, 30 mA, Type AC

MPN5SV4317-0KL
Active

Siemens SENTRON 5SV4317-0KL, 2-pole RCCB, 80 A rated, 30 mA trip, Type AC, instantaneous, DIN-rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SV4317-0KL — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV4317-0KL — Identification
ParameterValue
Product designationRCCB
Product design / constructionInstantaneous
5SV4317-0KL — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum45 °C
Minimum-25 °C
Width36 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SV4317-0KL — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

The Siemens SENTRON 5SV4317-0KL is a 2-pole residual current circuit breaker (RCCB) rated 80 A at 50 Hz, with a 30 mA trip threshold and Type AC sensitivity — meaning it detects sinusoidal AC fault currents only, not pulsed DC or smooth DC. It's an instantaneous design (no short-time delay), so it trips as soon as the residual current exceeds 30 mA. That makes it a straight ground-fault protector for general-purpose AC circuits where no delayed selectivity or DC component is expected. The 80 A rating holds at 40 °C ambient; derate to 77.87 A at 45 °C, 74.77 A at 50 °C, and so on down to 48.2 A at 70 °C. If your panel runs hot, the 80 A nameplate doesn't apply — check the derating curve.

Snaps onto DIN rail (REG), any mounting position. The 70 mm installation depth matches standard distribution board clearance; no extra depth needed behind the rail. Silicon-free construction, so it won't outgas contaminants near sensitive electronics.

Current production.

Fault ratings and standards

Short-circuit current rating (SCCR) is 10 kA per the general spec, with a lower 0.8 kA rating when tested per EN 60898 or IEC 61008-1 — the standard for RCCBs in household and similar installations. Let-through energy (I²t) is 110 000 A²·s permissible; let-through current peaks at 7 100 kA (likely a data-entry unit error — 7.1 kA peak is realistic for this class). Overvoltage category III, suitable for fixed-installation downstream of the service entrance.

Frequently asked questions

What is the rated tripping current of 5SV4317-0KL?

30 mA residual current, Type AC (sinusoidal AC fault detection only).

MPN