Siemens 5SV4346-0 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV4346-0 SENTRON RCCB, 63A 30mA 4P Type AC, 400V

MPN5SV4346-0
Active

Siemens SENTRON RCCB, 4-pole, Type AC, In: 63 A, 30 mA, Un AC: 400 V, order code 5SV4346-0.

$45.72Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SV4346-0 — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII
5SV4346-0 — Identification
ParameterValue
Product designationRCCB
Product design / constructionInstantaneous
5SV4346-0 — Mechanical
ParameterValue
Mounting positionany
Width in modular units4
Maximum45 °C
Minimum-25 °C
Width72 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SV4346-0 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

The Siemens 5SV4346-0 is a SENTRON residual current circuit breaker (RCCB), 4-pole, Type AC, rated 63 A with 30 mA sensitivity on a 400 V AC, 50 Hz supply.

Depth is 70 mm, height 90 mm. Grid spacing is 60 mm — standard for European distribution boards. Supply can land top or bottom. The IP20 rating is conditional on the distribution board being installed with conductors connected — expected for a panel-mount device.

Short-circuit and coordination

Rated short-circuit current is 10 kA per IEC 61008-1, with a permissible series fuse short-circuit current of 100 A. The rated impulse withstand voltage (overvoltage category III) suits fixed-installation downstream of the main panel.

Thermal and environmental limits

Silicon-free construction, which matters for potting or conformal-coating compatibility in sensitive electronics environments.

Frequently asked questions

Where can I buy 5SV4346-0 and get a price?

The 5SV4346-0 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the depth of 5SV4346-0?

The depth is 70 mm.

What is the width of 5SV4346-0?

The width is 72 mm, which corresponds to 4 modular width units.

Will 5SV4346-0 drop into a panel specified around 5SL4363-7?

Not without rewiring. The 5SL4363-7 is a 3-pole miniature circuit breaker (MCB) 54 mm wide, while the 5SV4346-0 is a 4-pole RCCB 72 mm wide. They serve different functions — overcurrent vs. earth fault protection — and occupy different panel footprints.

What compliance documentation does Siemens provide for 5SV4346-0?