Skip to main content
Siemens 5SV4444-0 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV4444-0 SENTRON RCCB, 4P, 40A, 100mA, 400V AC

MPN5SV4444-0
Active

Siemens SENTRON RCCB, 4-pole, Type AC, In: 40 A, 100 mA, Un AC: 400 V, 10 kA SCCR, DIN rail mount, 4 MW units.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SV4444-0 — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII
5SV4444-0 — Identification
ParameterValue
Product designationRCCB
Product design / constructionInstantaneous
5SV4444-0 — Mechanical
ParameterValue
Mounting positionany
Width in modular units4
Maximum45 °C
Minimum-25 °C
Width72 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SV4444-0 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

4-pole Type AC RCCB for 400 V line-to-line panels

The Siemens 5SV4444-0 is a SENTRON residual current circuit breaker (RCCB), 4-pole, Type AC, rated 40 A with a 100 mA residual trip threshold on a 230/400 V AC supply. The 70 mm installation depth matches standard SENTRON enclosure back-panel clearance. Mounting position is unrestricted — vertical or horizontal panel orientation works.

Type AC detection means it trips on sinusoidal AC residual currents only — suitable for circuits with resistive, inductive, or simple electronic loads where no pulsed DC or frequency-converter leakage is present. The 100 mA sensitivity is a high-threshold device, typically used for fire protection or equipment-level isolation rather than personnel shock protection (which requires ≤30 mA). Rated 230/400 V AC, so it handles both single-phase (L-N, 230 V) and three-phase (L-L, 400 V) circuits. Supply connection can be top or bottom — no mandatory orientation for line/load. IP20 with conductors connected — the enclosure must be closed during operation; this is standard for panel-mounted distribution gear, not for wet or outdoor locations without a higher-rated outer cabinet.

Frequently asked questions

How do I get current pricing and availability for 5SV4444-0?

The 5SV4444-0 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is 5SV4444-0's listed depth (70 mm) on this component line?

The 5SV4444-0 has a listed installation depth of 70 mm, matching standard SENTRON enclosure back-panel clearance.

What is 5SV4444-0's listed width (72 mm) on this component line?

The 5SV4444-0 is 72 mm wide, occupying 4 modular width units on a DIN rail.

Will 5SV4444-0 drop into a panel that was specified around 5SL4363-7 without rewiring?

No — the 5SL4363-7 is a 3-pole miniature circuit breaker (MCB) with a 54 mm width, while the 5SV4444-0 is a 4-pole RCCB at 72 mm. They serve different functions (overcurrent vs. residual current protection) and have different pole counts and widths, so a direct drop-in without rewiring is not possible.

MPN