Mounting position any; supply can come from top or bottom. Grid spacing 60 mm matches standard distribution board pitch. Silicon-free construction suits applications where outgassing must be avoided, like clean rooms or sealed enclosures.
At 45 °C it derates to 38.1 A, at 50 °C to 35.59 A, at 55 °C to 32.29 A, at 60 °C to 28.19 A, at 65 °C to 23.3 A, and at 70 °C to 17.6 A.
Fault energy and coordination
Let-through current permissible 5 200 A; I²t value 58 000 A²s. These numbers drive selectivity with upstream protective devices — the 5SV4614-0 lets through less energy than a typical 63 A MCB, so you can coordinate downstream without nuisance trips. Rated conditional short-circuit current per IEC 61008-1 is 0.5 kA — that's the withstand under the standard; the 10 kA SCCR is the practical interrupting rating for the installation.