Siemens 5SV4647-0 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV4647-0 SENTRON RCCB, 80 A, 300 mA, 4-pole

MPN5SV4647-0
Active

Siemens SENTRON RCCB, 4-pole Type AC, In: 80 A, IΔn: 300 mA, Un AC: 400 V, 10 kA SCCR, DIN rail mount, 4 MW.

$74.93Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV4647-0 — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII
5SV4647-0 — Identification
ParameterValue
Product designationRCCB
Product design / constructionInstantaneous
5SV4647-0 — Mechanical
ParameterValue
Mounting positionany
Width in modular units4
Maximum45 °C
Minimum-25 °C
Width72 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SV4647-0 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

The Siemens 5SV4647-0 is a SENTRON residual current circuit breaker (RCCB) — 4-pole, Type AC, rated 80 A with a 300 mA trip sensitivity on a 230/400 V AC supply. This is the instantaneous version (no short-time delay), so it clears earth faults without intentional lag, which matters when coordinating with downstream RCBOs or upstream time-delay RCDs in a distribution board.

The 300 mA sensitivity (Type AC) catches sinusoidal AC residual currents only — it is not rated for pulsed DC or smooth DC faults.