Skip to main content
Siemens 5SV4644-0KL — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV4644-0KL SENTRON RCCB, 4P, 40 A, 300 mA, Type AC

MPN5SV4644-0KL
Active

Siemens SENTRON RCCB, 4-pole, 40 A, 300 mA, Type AC, instantaneous, DIN rail, 70 mm depth, 72 mm width, 90 mm height.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV4644-0KL — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII
5SV4644-0KL — Identification
ParameterValue
Product designationRCCB
Product design / constructionInstantaneous
5SV4644-0KL — Mechanical
ParameterValue
Mounting positionany
Width in modular units4
Maximum45 °C
Minimum-25 °C
Width72 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SV4644-0KL — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

The 5SV4644-0KL: Rated 40 A at 40 °C, with a published derating curve: 38.1 A at 45 °C, stepping down to 17.6 A at 70 °C. The 300 mA trip threshold suits it for general-purpose earth-leakage protection in distribution boards — not for personnel protection (30 mA) or fire-prevention (300 mA is borderline). Snaps onto DIN rail (REG), occupies 4 modular-width units, and can be fed from top or bottom. IP20 with conductors connected — intended for enclosed distribution boards, not open-panel washdown areas.

Fault-current ratings and selectivity

Short-circuit current rating (SCCR) is 10 kA per the main spec; the conditional rating per EN 60898 and IEC 61008-1 is 0.8 kA. That 0.8 kA figure governs coordination with the upstream protective device — the RCCB itself is not a short-circuit interruption device, so the upstream MCB or fuse must clear faults above that level. Permissible let-through energy (I²t) is 58,000 A²·s; permissible let-through current is 5,200 kA — these bound the thermal and magnetic stress the device can withstand during a fault before the upstream protector opens.

Temperature and environment

Operating ambient -25 °C to 45 °C; storage -40 °C to 75 °C. Overvoltage category III, pollution degree unspecified but typical for distribution-board installation. Silicon-free construction.

Lifecycle status is 'current' — this is an active-production part.

Frequently asked questions

What is 5SV4644-0KL's listed depth?

The depth is 70 mm (installation depth also 70 mm). Width is 72 mm, height is 90 mm.

MPN
5SV4644-0KL