Skip to main content
Siemens 5SV5311-6KL — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV5311-6KL SENTRON RCCB, 2-pole, 16 A, 30 mA, Type

MPN5SV5311-6KL

Siemens SENTRON 5SV5311-6KL, residual current operated circuit breaker (RCCB), 2-pole, Type A, In: 16 A, 30 mA, Un AC: 230 V, N left, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV5311-6KL — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV5311-6KL — Identification
ParameterValue
Product designationRCCB
Product design / constructionInstantaneous
5SV5311-6KL — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum45 °C
Minimum-25 °C
Width36 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SV5311-6KL — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

The Siemens 5SV5311-6KL is a 2-pole residual current operated circuit breaker (RCCB) from the SENTRON family, rated 16 A at 230 V AC, 50 Hz, with a 30 mA trip threshold and Type A residual current sensitivity.

The 30 mA trip current (Type A) catches pulsating DC fault currents as well as sinusoidal AC — common in circuits with rectifiers, variable-speed drives, or switching power supplies. The instantaneous design (no short-time delay) trips within milliseconds, which is standard for personnel protection but means it may nuisance-trip on high inrush loads like motor starting — check coordination if feeding inductive gear.

Mounts on DIN rail (REG) in any position. Depth is 70 mm, which matches the standard 70 mm installation depth of most SENTRON modular devices — no extra clearance needed behind the rail. Supply can enter from top or bottom. The N-left variant means the neutral busbar connects on the left side of the device; verify busbar orientation before wiring. IP20 rating applies only when installed in a distribution board with connected conductors — not for open-panel use.

Frequently asked questions

What is 5SV5311-6KL's listed depth (70 mm) on this component line?

The depth is 70 mm, which is the standard installation depth for SENTRON modular devices — no extra clearance behind the DIN rail is needed beyond that.

What is 5SV5311-6KL's listed width (36 mm) on this component line?

The width is 36 mm, corresponding to 2 modular width units on a DIN rail. This matches the footprint of most 2-pole SENTRON breakers and RCCBs, so it fits existing busbar and wiring layouts.

MPN
5SV5311-6KL