Skip to main content
Siemens 5SV5314-0FC — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV5314-0FC SENTRON RCCB 2P 40A 30mA Type AC 230V

MPN5SV5314-0FC

Siemens SENTRON RCCB, 2-pole, Type AC, In: 40 A, 30 mA, Un AC: 230 V, 6 kA SCCR, instantaneous, DIN rail mount, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV5314-0FC — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV5314-0FC — Identification
ParameterValue
Product designationRCCB
Product design / constructionInstantaneous
5SV5314-0FC — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum45 °C
Minimum-25 °C
Width36 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SV5314-0FC — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

RCCB for personnel and fire protection on 230 V single-phase circuits

The Siemens 5SV5314-0FC is a 2-pole residual current operated circuit breaker (RCCB) from the SENTRON family, rated 40 A at 230 V AC with a 30 mA trip threshold.

Mounting position is unrestricted — horizontal or vertical in the enclosure. Supply can land top or bottom terminals. Installation depth matches the unit depth at 70 mm, so it sits flush with other SENTRON 2-MU devices on the same rail. IP20 rating applies once the distribution board is installed with conductors connected.

Fault ratings and coordination

Rated short-circuit current (IEC 61008-1) is 0.5 kA, and the conditional short-circuit current rating with an associated upstream MCB or fuse is 6 kA. The permissible let-through current is 5 200 A; the I²t value is 58 000 A²·s. These numbers define the energy-limiting capability during a fault — useful for selectivity studies with downstream breakers. Operating frequency is 50 Hz only.

Frequently asked questions

What is the difference between this 5SV5314-0FC Type AC RCCB and a Type A RCCB?

Type AC detects sinusoidal AC residual currents only. Type A adds detection for pulsed DC residual currents (e.g., from rectifiers, switching power supplies, or variable-speed drives). If the downstream loads include electronics, a Type A device is required by most wiring regulations.

What is 5SV5314-0FC's rated short-circuit current?

The rated conditional short-circuit current is 6 kA per IEC 61008-1, with an associated upstream overcurrent protective device. The I²t value is 58 000 A²·s.

Where can I buy 5SV5314-0FC?

The 5SV5314-0FC is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

MPN
5SV5314-0FC