It operates on 230/400 V AC at 50 Hz and carries a 6 kA short-circuit current rating per IEC 61008-1.
Depth is 70 mm, so it sits flush with most domestic consumer units. Mounting position is unrestricted — top or bottom feed works. IP20 with connected conductors in an installed distribution board; fine for enclosed panels, not for open washdown areas. Silicon-free construction suits environments where silicone outgassing can foul relay contacts or optical sensors.
The 30 mA trip is the IEC 60364-mandated threshold for socket-outlet circuits in dwellings. Type A detection covers sinusoidal AC and pulsating DC waveforms, so it handles modern electronics (washing machines, LED drivers, VFDs) that generate half-wave rectified leakage. Ambient range -5 °C to 45 °C covers most indoor board environments; storage down to -40 °C allows winter site storage without damage.