Siemens 5SV5316-0MB — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV5316-0MB SENTRON RCCB, 2-pole, 63 A, 30 mA, Type

MPN5SV5316-0MB

Siemens SENTRON RCCB, 2-pole, Type AC, 63 A, 30 mA, 230 V AC, 60 Hz, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV5316-0MB — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV5316-0MB — Identification
ParameterValue
Product designationRCCB
Product design / constructionInstantaneous
5SV5316-0MB — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum45 °C
Minimum-25 °C
Width36 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SV5316-0MB — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

The Siemens 5SV5316-0MB is a SENTRON residual current circuit breaker (RCCB), 2-pole, Type AC, rated 63 A with a 30 mA trip threshold for 230 V AC, 60 Hz circuits.

The 63 A rating matches a typical main-switch or heavy-load subfeed; at 40 °C it holds the same 63 A, so no derating needed at normal panel ambient. The 6 kA short-circuit current rating is the breaking capacity under fault — adequate for most domestic and small commercial service entrances, but check your available fault current if you're feeding from a large transformer. It's Type AC, meaning it detects sinusoidal AC residual currents only; if your load includes rectifiers, VFDs, or switched-mode supplies, you'd want a Type A or F instead.

Panel integration and compliance

Supply can enter from top or bottom. The IP20 rating is standard for enclosed distribution boards — it's not a standalone outdoor device. Overvoltage category III suits fixed installation downstream of the utility meter.

Frequently asked questions

Will 5SV5316-0MB drop into a panel specified around 5SY7206-7CC without rewiring?

They share the same 36 mm width (2 MW) and 70 mm installation depth, and both mount on DIN rail. The physical fit is the same — same footprint, same clip-on method. But the 5SY7206-7CC is a miniature circuit breaker (overcurrent + short-circuit), while the 5SV5316-0MB is an RCCB (residual-current only). You can swap the hardware into the same DIN slot, but the circuit function is different; the wiring and protection scheme must match the device type.

MPN
5SV5316-0MB