Siemens 5SV5316-6 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV5316-6 SENTRON RCCB, 63A 30mA Type A, 2-Pole

MPN5SV5316-6
Active

Siemens SENTRON 5SV5316-6 RCCB, 2-pole, Type A, 63 A rated, 30 mA trip, 230 V AC, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV5316-6 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV5316-6 — Identification
ParameterValue
Product designationRCCB
Product design / constructionInstantaneous
5SV5316-6 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum45 °C
Minimum-5 °C
Width36 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SV5316-6 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

The 70 mm depth matches the typical flush-mount distribution board depth, so it sits flush with the front cover when installed.

For reference, the conditional short-circuit rating per EN 60898 is 0.8 kA, and per IEC 61008-1 it is also 0.8 kA; these apply when the RCCB is backed by an upstream overcurrent device. The 30 mA rated residual operating current is the trip threshold for earth leakage. At this sensitivity the device meets the touch-voltage protection requirements of IEC 60364 for socket-outlet circuits and hand-held equipment. The instantaneous design (no intentional delay) means it trips within 40 ms at rated residual current — fast enough to limit let-through energy to 110 000 A²·s and peak let-through current to 7 100 A under fault. The IP20 rating is standard for enclosed distribution boards — the RCCB is not intended for wet or dust-exposed locations without an outer enclosure.

The silicon-free construction is relevant for potting or conformal-coating processes where silicone outgassing can cause adhesion failures. Mechanical life is rated at 3 000 switching cycles — typical for an RCCB that operates infrequently as a protective device, not a daily-use switch.

Frequently asked questions

Where can I buy 5SV5316-6 and get a price?

The 5SV5316-6 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

Will 5SV5316-6 drop into a panel specified around 5SU9354-7KK16 without rewiring?

Physically yes — both are 2 MW wide (36 mm), DIN-rail mounted, 70 mm depth, and accept top or bottom feed. The difference is functional: the 5SU9354-7KK16 is an RCBO (RCD + MCB), while the 5SV5316-6 is an RCCB only. If the circuit requires overcurrent protection, the 5SV5316-6 must be paired with a separate MCB upstream.

What compliance documentation does Siemens provide for 5SV5316-6?

The 5SV5316-6 is designed to EN 60898 and IEC 61008-1. It carries an IP20 protection class (enclosed board) and is rated for overvoltage category III. Silicon-free construction is declared. For specific RoHS, REACH, or UL documentation, request the manufacturer's declaration of compliance with your RFQ.