The Siemens SENTRON 5SV5346-0 is a 4-pole residual current circuit breaker (RCCB), rated 63 A with 30 mA trip sensitivity, Type AC, for 400 V AC at 50 Hz.
Depth is 70 mm, height 90 mm, width 72 mm (4 MW). Grid spacing is 60 mm.
The 63 A rated current means it handles the full load of a large submain or a high-current final circuit. Type AC detection means it trips on sinusoidal AC residual currents only — not suitable for pulsating DC or smooth DC fault currents (those require Type A or Type B). The 6 kA short-circuit current rating (IEC 61008-1) is the withstand rating; upstream overcurrent protection must limit fault energy to this level.