Skip to main content
Siemens 5SV5346-6KL — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV5346-6KL SENTRON RCCB, 4P, 63 A, 400 V, Type A

MPN5SV5346-6KL

Siemens SENTRON 5SV5 series, RCCB, 4-pole, 63 A rated current, 400 V AC, Type A fault current, instantaneous, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV5346-6KL — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII
5SV5346-6KL — Identification
ParameterValue
Product designationRCCB
Product design / constructionInstantaneous
5SV5346-6KL — Mechanical
ParameterValue
Mounting positionany
Width72 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SV5346-6KL — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

The Siemens 5SV5346-6KL is a 4-pole residual current circuit breaker (RCCB) from the SENTRON 5SV5 series, rated for 63 A at 400 V AC and designed to detect Type A fault currents — AC sinusoidal and pulsating DC — making it a fit for mixed-load panels with electronics, drives, or rectifiers. It carries a 10 kA short-circuit current rating (SCCR). The unit is instantaneous (no short-time delay), meaning it trips within milliseconds on a residual current — standard for general-purpose shock protection in distribution boards.

Snaps onto DIN rail (REG mounting) and occupies 4 width units (72 mm wide) — standard 4-pole RCCB footprint for a 400 V three-phase + N panel. Depth is 70 mm, same as installation depth; height is 90 mm. Supply can land top or bottom; neutral is on the left (N left variant).

Thermal performance and derating

At 65 °C it drops to 57.35 A, and at 70 °C to 48.84 A.

MPN
5SV5346-6KL