Siemens 5SV5416-0 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV5416-0 SENTRON RCCB, 63 A, 100 mA, Type AC, 2-pol

MPN5SV5416-0
Active

Siemens SENTRON 5SV5416-0, RCCB, 2-pole, Type AC, 63 A, 100 mA, 230 V AC, 50 Hz, 6 kA, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SV5416-0 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SV5416-0 — Identification
ParameterValue
Product designationRCCB
Product design / constructionInstantaneous

Mechanical

5SV5416-0 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum45 °C
Minimum-25 °C
Width36 mm
Height90 mm
Depth70 mm
Installation depth70 mm

Environmental

5SV5416-0 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

What this RCCB does on the line

The Siemens SENTRON 5SV5416-0 is a 2-pole residual current operated circuit breaker (RCCB), Type AC, rated 63 A with a 100 mA trip threshold. It operates on 230 V AC at 50 Hz, with a short-circuit current rating of 6 kA. The instantaneous design means no intentional delay — it trips as soon as the residual current exceeds 100 mA, which is the standard choice for general-purpose protection against sinusoidal AC fault currents in residential and light commercial panels.

DIN rail fit and panel integration

Mounts on standard DIN rail (REG) per, occupying 2 modular width units (36 mm wide). Depth is 70 mm — the same as the installation depth, so no extra clearance needed behind the rail. Mounting position is unrestricted (any orientation). Supply can enter from top or bottom. The IP20 rating applies when installed in a distribution board with conductors connected — standard for enclosed panel use.

Ratings and what they mean for selection

Rated 63 A at both 40 °C and at AC — no derating needed up to that ambient. The 6 kA SCCR (IEC 61008-1 / EN 60898) is the maximum prospective fault current the device can safely interrupt. The 100 mA sensitivity is higher than the typical 30 mA for personal shock protection; it's used where the goal is fire protection or equipment protection on circuits with higher natural leakage. The I²t let-through of 110,000 A²s and peak let-through current of 7,100 A are the energy and current the RCCB allows downstream during a fault — useful for coordinating with downstream MCBs. Overvoltage category III means it's rated for fixed installation downstream of the main distribution board.

Frequently asked questions

What is the 5SV5416-0 used for?

It is a 2-pole Type AC RCCB rated 63 A / 100 mA, used for residual current protection on 230 V AC, 50 Hz single-phase circuits. The 100 mA sensitivity suits fire protection or equipment protection on circuits with higher natural leakage current.

How do I get pricing and availability for 5SV5416-0?

Submit an RFQ through this listing. The part is sourced to order through independent distribution; current pricing and stock position are confirmed at quote time.

Does 5SV5416-0 fit a panel designed for 5SL6550-7BB?

Both are 2-pole, 36 mm wide, 90 mm tall, DIN rail mounted, with the same 70 mm installation depth. The 5SL6550-7BB is an MCB, not an RCCB, so the function differs, but the mechanical footprint is identical — no rewiring of the DIN rail or enclosure cutout is needed.

What compliance documentation does Siemens provide for 5SV5416-0?

The part carries IEC 61008-1 and EN 60898 ratings (0.8 kA Icn). The SENTRON series typically includes CE, UKCA, and EAC declarations; specific certificates should be requested with the RFQ. The product is silicon-free and rated for overvoltage category III.

MPN
5SV5416-0