Skip to main content
Siemens 5SV6016-6GV25 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV6016-6GV25 SENTRON AFDD-MCB B25 6kA 1P+N

MPN5SV6016-6GV25
Active

Siemens SENTRON 5SV6016-6GV25 AFDD-MCB combination, 1P+N, 25 A, B curve, 6 kA breaking capacity, 18 mm width, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV6016-6GV25 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV6016-6GV25 — Identification
ParameterValue
Product designationAFDD-MCB combination
Product design / constructionCompact unit
5SV6016-6GV25 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height90 mm
Depth68.5 mm
Installation depth70 mm
5SV6016-6GV25 — Environmental
ParameterValue
IP degree of protectionIP20, with connected protective device and conductors
5SV6016-6GV25 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

The B curve (3-5 In magnetic trip) suits resistive and general-purpose loads like lighting and socket outlets where inrush is low.

Snaps onto DIN rail (REG) and occupies a single modular width of 18 mm, so it fits standard 1-MW cutouts in consumer units and sub-distribution boards. The 68.5 mm depth leaves clearance for cover-mounted busbars and cable ducts in a typical 70 mm installation depth enclosure. IP20 with conductors connected — fine for dry indoor panels; no washdown rating. Mounting position is unrestricted, which simplifies layout in tight enclosures.

Frequently asked questions

Where can I buy the 5SV6016-6GV25 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no online stock figure or price is published here.

What is the breaking capacity of the 5SV6016-6GV25?

6 kA per both EN 60898-1 and IEC 60947-2, which is the standard interrupting rating for residential final-circuit breakers at 230 V AC.

Will the 5SV6016-6GV25 drop into a panel designed for a 5SL6006-7?

Both are 1-module-width (18 mm) DIN-rail devices with the same 90 mm height and similar depth (68.5 mm vs 76 mm). The 5SL6006-7 is a plain MCB (C-curve, no AFD), while the 5SV6016-6GV25 is an AFDD-MCB combination — so the footprint fits, but the wiring and protection function differ. No rewiring of the busbar is needed, but the neutral connection and arc-fault detection add a terminal.

MPN
5SV6016-6GV25