Siemens 5SV6016-6KK10 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV6016-6KK10 SENTRON AFDD-MCB, 10A B-curve, 6kA

MPN5SV6016-6KK10
Active

Siemens SENTRON AFDD-MCB combination, 1P+N, 10 A, B-curve, 6 kA, 1 MW modular width, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV6016-6KK10 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV6016-6KK10 — Identification
ParameterValue
Product designationAFDD-MCB combination
Product design / constructionCompact unit
5SV6016-6KK10 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height90 mm
Depth68.5 mm
Installation depth70 mm
5SV6016-6KK10 — Environmental
ParameterValue
IP degree of protectionIP20, with connected protective device and conductors
5SV6016-6KK10 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

Arc-fault and overcurrent in one 18 mm slot

The Siemens 5SV6016-6KK10 is a SENTRON AFDD-MCB combination — an arc-fault detection device (AFDD) and miniature circuit breaker (MCB) rolled into a single 1 MW (18 mm wide) compact unit. It protects a 230 V AC, 50 Hz, 1P+N final circuit at 10 A with a B-curve trip characteristic, and interrupts fault currents up to 6 kA per both EN 60898-1 and IEC 60947-2. That 6 kA rating is the same under either standard, so you don't have to derate or double-check which code governs the installation.

The B-curve (trips at 3–5× In) means this unit is sized for resistive or light inductive loads — lighting, small heaters, control transformers — not motor starting or high-inrush gear. The 1P+N design switches the line conductor and switches the neutral, but does not protect the neutral — the neutral pole is a switching pole only.

Mounting and environment

Depth is 68.5 mm, installation depth 70 mm — that extra 1.5 mm accounts for the DIN rail clip clearance behind the panel door. IP20 with conductors connected means it's finger-safe once wired, but not protected against water ingress — keep it inside the enclosure.

Frequently asked questions

What is 5SV6016-6KK10's depth and width?

Depth is 68.5 mm (installation depth 70 mm) and width is 18 mm (1 modular width unit).

Can 5SV6016-6KK10 replace a standard MCB like 5SY4116-7CV in an existing panel?

Not directly — the 5SV6016-6KK10 is an AFDD-MCB combination (arc-fault detection plus overcurrent) while the 5SY4116-7CV is a standard MCB. Both mount on DIN rail at 18 mm width, but the AFDD adds arc-fault detection electronics that may require different wiring (neutral switching) and has a 6 kA breaking capacity versus 15 kA for the 5SY4116-7CV. Check if the circuit requires arc-fault protection before substituting.

Where can I buy 5SV6016-6KK10?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.