Skip to main content
Siemens 5SV6016-6MC16 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV6016-6MC16 SENTRON AFDD-MCB, 1P+N, B-char, 6 kA

MPN5SV6016-6MC16

Siemens SENTRON AFDD-MCB combination, 5SV6016-6MC16, 1P+N, B-characteristic, 6 kA breaking capacity, integrated metering, 1 MW wide, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV6016-6MC16 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV6016-6MC16 — Identification
ParameterValue
Product designationAFDD-MCB combination
Product design / constructionCompact unit
5SV6016-6MC16 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height90 mm
Depth68.5 mm
Installation depth70 mm
5SV6016-6MC16 — Environmental
ParameterValue
IP degree of protectionIP20, with connected protective device and conductors
5SV6016-6MC16 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

The Siemens 5SV6016-6MC16 is a SENTRON AFDD-MCB combination — a single compact unit that packs arc-fault detection, overcurrent protection, and energy metering into one 18 mm-wide module (one modular width). It protects a 1P+N circuit with a B tripping characteristic and a 6 000 A breaking capacity per EN 60898-1, meaning it clears short-circuit faults up to 6 kA at 230 V AC without needing an upstream fuse backup in most residential or light-commercial panels.

Integrated metering — what you can read off the front

Unlike a plain MCB, this unit includes a voltmeter, ammeter, wattmeter, frequency meter, and reactive-power meter — all visible on the front display. Accuracy for current and voltage is 0.5 %, for active power 1 %, per IEC 61557-12, IEC 62053-22, and IEC 62053-23. The display cycles through voltage, current, active/apparent/reactive power, active energy, line frequency, power factor, temperature, switching cycles, operating hours, tripping events, and warnings — enough data to trend a circuit's health without a separate power meter.

Where it fits — panel integration and environment

Depth is 68.5 mm, installation depth 70 mm — it clears most shallow enclosures. Rated IP40 on the front, IP20 at the rear (with conductors and protective device connected).

Compliance and ruggedness notes

Tested for shock and vibration per IEC 61373, so it holds up in rail-vehicle or mobile-equipment panels. Supports a wireless protocol for data readout — no separate communication module needed to pull metering data off the unit.

Frequently asked questions

What metering values does the 5SV6016-6MC16 display?

Voltage, current, active/apparent/reactive power, active energy, line frequency, power factor, temperature, switching cycles, operating hours, tripping events, and warnings.

Does 5SV6016-6MC16 drop into a panel specified for 5SL3116-6MB?

Both mount on standard DIN rail, but the 5SV6016-6MC16 is an AFDD-MCB combination with integrated metering, while the 5SL3116-6MB is a standard MCB without arc-fault detection or metering. The footprint is the same 1 MW width, so mechanical fit is identical, but the wiring and functional requirements differ — the AFDD needs a neutral connection for arc-fault detection.

MPN
5SV6016-6MC16