Siemens 5SV6016-7GV06 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV6016-7GV06 SENTRON AFDD/MCB, 6 A, 6 kA, 1P+N

MPN5SV6016-7GV06
Active

Siemens SENTRON AFDD/MCB, 6 A, 230 V AC, 6 kA, 1P+N, 18 mm wide, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV6016-7GV06 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV6016-7GV06 — Identification
ParameterValue
Product designationArc-fault detection unit MCB
Product design / constructionCompact unit
5SV6016-7GV06 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height90 mm
Depth68.5 mm
Installation depth70 mm
5SV6016-7GV06 — Environmental
ParameterValue
IP degree of protectionIP20, with connected protective device and conductors
5SV6016-7GV06 — Electrical
ParameterValue
Operational current / at AC / rated value6 A

Product details

The Siemens 5SV6016-7GV06 is a SENTRON arc-fault detection unit combined with a miniature circuit breaker (AFDD/MCB). It protects a 230 V AC final circuit against both overload/short-circuit and series or parallel arcing faults — the kind of low-energy, high-resistance arcs a standard MCB won't clear. The 1P+N configuration switches the line conductor only; the neutral is switched through but not protected. Installation depth is 70 mm, with the device body itself 68.5 mm deep.

Arc-fault detection — what the thresholds mean

The AFDD detects two arc modes. For series arcs (a loose connection or broken conductor in line with the load), the detection window runs from 1 A minimum up to 6 A maximum — right at the MCB's thermal rating, so it catches an arcing fault before the breaker's overcurrent trip would operate. For parallel arcs (line-to-neutral or line-to-ground), the detection range is 50 A minimum to 500 A maximum, covering the high-energy fault path. The unit does not include a short-time delay on the switching function; it trips instantaneously on arc detection. That 50 A minimum parallel-arc threshold is worth noting: it means the AFDD will not nuisance-trip on normal inrush from a motor or capacitive load that stays below that current level. The 500 A ceiling covers most branch-circuit arc faults without waiting for the MCB's magnetic trip at 6 kA.

Panel fit and environmental tolerance

Snaps onto DIN rail (REG) in any orientation.

Frequently asked questions

What is the breaking capacity of 5SV6016-7GV06?

6 kA rated according to both EN 60898-1 and IEC 60947-2.

Where can I buy 5SV6016-7GV06 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock figures or prices are published here.

What does the AFDD detect — series arcs, parallel arcs, or both?

Both. Series arcs are detected from 1 A to 6 A; parallel arcs from 50 A to 500 A.