Skip to main content
Siemens 5SV6016-7KK20 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV6016-7KK20 SENTRON AFDD+MCB, 20A, C-Curve, 1P+N

MPN5SV6016-7KK20
Active

Siemens SENTRON 5SV6016-7KK20 AFDD-MCB combination, 230 V AC, 20 A, C-curve, 1P+N, 6 kA breaking capacity, 1 MW modular width, DIN rail mount.

$246.53 – $260.41Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV6016-7KK20 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV6016-7KK20 — Identification
ParameterValue
Product design / constructionCompact unit
5SV6016-7KK20 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height90 mm
Depth68.5 mm
Installation depth70 mm
5SV6016-7KK20 — Environmental
ParameterValue
IP degree of protectionIP20, with connected protective device and conductors
5SV6016-7KK20 — Electrical
ParameterValue
Tripping Characteristic ClassC
Operational current / at AC / rated value20 A

Product details

AFDD-MCB combination, 20 A, C-curve, 1P+N

The Siemens 5SV6016-7KK20 is a compact AFDD-MCB combination from the SENTRON series, integrating arc-fault detection with overcurrent protection in a single 1 MW modular-width unit for 230 V AC residential and commercial final circuits. Rated 20 A with a C-curve tripping characteristic, it protects against both overload and short-circuit conditions up to 6 kA per EN 60898-1 and IEC 60947-2 — the standard breaking capacity for most domestic distribution boards. The 1P+N pole configuration switches the line conductor while the neutral is switched internally, suiting single-phase circuits where neutral isolation is required for the AFDD function.

Arc-fault detection range and selectivity

The AFDD detects series arcs between 2 A and 20 A and parallel arcs between 50 A and 500 A — the lower threshold catches glowing connections at the back of a junction box that a standard MCB would never trip on. Because the unit combines AFDD and MCB in one housing, there is no separate arc-fault sensor to mount in the panel — the entire protection chain lives in 18 mm of DIN-rail space.

Mechanical and environmental ratings

Rated for ambient temperatures from -40 °C to 75 °C, with a 55 °C limit at 95% relative humidity — covers unconditioned enclosures in both cold storage and plant-floor environments. The housing is halogen-free and silicon-free, meeting the material restrictions common in rail, marine, and clean-room installations where outgassing can damage nearby contacts or optics. IP20 protection applies with conductors connected; the device is rated for overvoltage category III and pollution degree 2, the standard specification for fixed-installation distribution boards.

Mounting and panel integration

Snaps onto DIN rail (REG) and occupies 1 modular width unit (18 mm) with a 70 mm installation depth — fits standard consumer units and sub-distribution boards without extra space. Mounting position is unrestricted, and the supply connection can be made from either end — useful when retrofitting into an existing board where the busbar orientation is fixed. The 68.5 mm depth leaves clearance behind most standard enclosure covers; verify the cover depth if the board uses a shallow trim plate.

Lifecycle and sourcing position

No stock-holding claim is made here. The mechanical service life is rated at 10,000 switching cycles typical — sufficient for branch-circuit protection in residential and light commercial panels where the device operates infrequently.

MPN
5SV6016-7KK20