It integrates arc-fault detection (AFDD per IEC 62606), 30 mA type A residual current protection, and a B-curve overcurrent characteristic into one 1-module-wide (18 mm) package that snaps onto a DIN rail. That means a single device covers series arc faults, ground faults, and overload/short-circuit protection for a final subcircuit — no need to stack an AFDD ahead of an RCBO.
Rated 32 A with B-curve tripping: the magnetic trip operates between 3 and 5 times rated current (96–160 A), so it suits resistive and light inductive loads like lighting, socket outlets, and small appliances where inrush is modest.
Depth is 68.5 mm (70 mm installation depth), which clears most standard enclosure gland plates.
Halogen-free and silicon-free construction — important for outgassing-sensitive environments like data centers, medical facilities, or clean rooms.