Skip to main content
Siemens 5SV6316-7KK06 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV6316-7KK06 SENTRON AFDD-RCBO, 6A C-curve, 30mA, 1

MPN5SV6316-7KK06
Active

Siemens SENTRON AFDD-RCBO, 230 V AC, 6 A, C characteristic, 30 mA residual current, 1P+N, 6 kA, 1 MW, compact.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV6316-7KK06 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV6316-7KK06 — Identification
ParameterValue
Product designationAFDD-RCBO
Product design / constructionCompact unit
5SV6316-7KK06 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height90 mm
Depth68.5 mm
Installation depth70 mm
5SV6316-7KK06 — Environmental
ParameterValue
IP degree of protectionIP20, with connected protective device and conductors
5SV6316-7KK06 — Electrical
ParameterValue
Tripping Characteristic ClassC
Operational current / at AC / rated value6 A

Product details

Arc-fault and residual-current protection in one 18 mm slot

The Siemens SENTRON 5SV6316-7KK06 is a combined arc-fault detection device and residual-current circuit breaker (AFDD-RCBO) that packs overcurrent, earth leakage, and series/parallel arc-fault protection into a single 18 mm-wide module.

The 6 A rated current with C-curve magnetic release suits circuits with moderate inrush — think lighting banks, socket outlets, or small appliance groups. The 30 mA residual-current element (type A) detects pulsating DC fault currents common in electronics, so it covers modern loads with rectified front ends. Arc-fault detection covers both series arcs (2 A to 6 A) and parallel arcs (50 A to 500 A), addressing the two main failure modes that standard MCBs and RCCBs cannot see. The 1-pole + N design switches the phase and monitors the neutral; the neutral pole is switched, not just sensed, which matters for full isolation.

Mounting position is unrestricted — the arc-fault detection electronics are orientation-independent.

Frequently asked questions

Where can I buy 5SV6316-7KK06 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead-time estimate.

What is the depth of 5SV6316-7KK06?

The device depth is 68.5 mm, with an installation depth of 70 mm. The 18 mm width occupies one modular unit on DIN rail.

Will 5SV6316-7KK06 drop into a panel specified around 5SY3025-7KL?

The 5SV6316-7KK06 is a combined AFDD-RCBO, whereas the 5SY3025-7KL is a standard MCB without arc-fault or residual-current functionality. They share the same 18 mm DIN-rail footprint and 1 MW form factor, so the physical fit is the same, but the 5SV6316-7KK06 adds arc-fault detection and RCD protection that the MCB does not provide. Rewiring the neutral connection is required because the AFDD-RCBO switches the neutral pole.

What compliance documentation does Siemens provide for 5SV6316-7KK06?

The device is halogen-free and silicon-free. Breaking capacity is certified to both IEC 60898-1 and IEC 60947-2 at 6 kA. Standard Siemens declarations of conformity (CE, UKCA) and RoHS/REACH statements are available through the product documentation portal.

MPN