Skip to main content
Siemens 5SV6316-7KK25 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV6316-7KK25 AFDD-RCBO, 25A, 30mA, 6kA, 1P+N

MPN5SV6316-7KK25
Active

Siemens SENTRON 5SV6316-7KK25, AFDD-RCBO, 1P+N, 25 A, 30 mA, 6 kA, C-curve, Type A, 1 MW, 230 V AC, 50 Hz.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV6316-7KK25 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV6316-7KK25 — Identification
ParameterValue
Product designationAFDD-RCBO
Product design / constructionCompact unit
5SV6316-7KK25 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height90 mm
Depth68.5 mm
Installation depth70 mm
5SV6316-7KK25 — Environmental
ParameterValue
IP degree of protectionIP20, with connected protective device and conductors
5SV6316-7KK25 — Electrical
ParameterValue
Tripping Characteristic ClassC
Operational current / at AC / rated value25 A

Product details

The Siemens SENTRON 5SV6316-7KK25 is a compact AFDD-RCBO — an arc-fault detection device combined with a residual current circuit breaker in a single 18 mm wide unit. It protects a 1P+N circuit at 230 V AC, 50 Hz, with a 25 A rated current and 30 mA residual sensitivity, Type A.

The 30 mA residual current (Type A) catches sinusoidal AC and pulsed DC fault currents — covers most modern electronics and variable-speed drives. The AFDD function detects series arcs (2 A to 25 A) and parallel arcs (50 A to 500 A), so it protects against loose connections and damaged cable insulation that a standard RCBO would miss.

Integration notes

Accepts conductors up to the terminal rating; spring-cage or screw terminals depending on variant — verify termination style on the nameplate. Halogen-free and silicon-free construction suits clean-room or low-outgassing environments. The test button requires a minimum 195 V AC to operate correctly.

Frequently asked questions

Where can I buy 5SV6316-7KK25 and get pricing?

The 5SV6316-7KK25 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the closest functional second-source for 5SV6316-7KK25?

The 5SL4106-7CC is a close functional sibling — also a 1P+N RCBO, 25 A, 30 mA, C-curve, Type A, 6 kA, but it lacks the integrated AFDD (arc-fault detection). If your application requires arc-fault protection, the 5SV6316-7KK25 is the correct choice; the 5SL4106-7CC will not detect series or parallel arcs.

Will 5SV6316-7KK25 drop into a panel specified around 5SL4106-7CC without rewiring?

Yes — both are 1P+N, 18 mm wide, DIN-rail mounted, and share the same 25 A / 30 mA / C-curve / Type A / 6 kA ratings. The 5SV6316-7KK25 is deeper (68.5 mm vs the 5SL4106-7CC's typical depth), so check the enclosure depth clearance (70 mm minimum installation depth required) before swapping.

What compliance documentation does Siemens provide for 5SV6316-7KK25?

The manufacturer provides declarations of conformity for RoHS, REACH, and the applicable product standards (IEC 60947-2, EN 60898-1). Request the specific documents with your RFQ.

MPN