5SV9313-1CN06 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV9313-1CN06 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous
5SV9313-1CN06 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SV9313-1CN06 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SV9313-1CN06 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens SENTRON 5SV9313-1CN06 is an RCD-operated circuit breaker (RCBO) combining overcurrent protection and residual current protection in a single 18 mm-wide module. Breaking capacity is 4.5 kA per EN 60898 and 5 kA per IEC 60947-2. For a domestic or light commercial distribution board fed from a transformer of typical impedance, that covers most fault scenarios downstream of a 63 A or smaller incoming device. The 1P+N design switches the line conductor and monitors the neutral; it occupies one modular width (18 mm) on the DIN rail, which is tight for an RCBO — most competitors need two widths for a combined device.

Thermal derating and installation

The 6 A rating holds at 30 °C ambient; at 40 °C it derates to 5.64 A, at 45 °C to 5.46 A, and at 55 °C to 5.04 A. In a crowded panel with multiple RCBOs side by side, the internal temperature rise reduces the usable current — plan the load at the derated figure for the expected cabinet ambient. Depth is 77 mm, installation depth 70 mm, height 90 mm.

Frequently asked questions

What is the breaking capacity of this RCBO?

Rated breaking capacity is 4.5 kA per EN 60898 and 5 kA per IEC 60947-2.

What is the residual current sensitivity and type?

Tripping fault current is 30 mA, residual current type AC — detects sinusoidal AC fault currents.

How does the 5SV9313-1CN06 compare to a standard MCB like the 5SL4106-7CC?

The 5SL4106-7CC is a Siemens SENTRON MCB with the same 6 A C-curve rating but no residual current protection — it occupies one modular width and protects only against overload and short circuit. The 5SV9313-1CN06 adds 30 mA RCD protection in the same 18 mm footprint, combining two functions where the MCB alone would need a separate RCCB. If your panel already has a shared RCD upstream, the MCB is sufficient; if you need per-circuit earth-fault protection, the RCBO is the direct fit.

Where can I buy 5SV9313-1CN06 and get current pricing?