Skip to main content
Siemens 5SV9313-7CN10 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV9313-7CN10 SENTRON RCBO, 10 A, 30 mA, Type A, C-c

MPN5SV9313-7CN10

Siemens SENTRON 5SV9313-7CN10, RCBO, 2-pole 1P+N, 10 A rated, 30 mA Type A residual current, C-curve, 4.5 kA (EN 60898).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV9313-7CN10 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV9313-7CN10 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous
5SV9313-7CN10 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SV9313-7CN10 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SV9313-7CN10 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens 5SV9313-7CN10 is a SENTRON RCBO — a residual-current-operated circuit breaker that packs overcurrent and earth-leakage protection into a single 18 mm-wide module. It's a 2-pole, 1P+N unit with a 10 A rated current and a 30 mA Type A residual-current trip. The C-curve characteristic means it handles moderate inrush (like small motors or lighting ballasts) without nuisance tripping. Rated breaking capacity is 4.5 kA per EN 60898 and 5 kA per IEC 60947-2 — enough for most residential and light commercial distribution boards.

Thermal derating — the real-world current

At 40 °C it derates to 9.4 A, at 45 °C to 9.1 A, at 50 °C to 8.7 A, and at 55 °C to 8.4 A. If your panel runs warm — say, next to a drive or in a sunlit enclosure — size the load against the derated figure, not the label.

Snaps onto DIN rail, takes one modular width unit (18 mm). Depth is 77 mm, height 90 mm, installation depth 70 mm. Mounting position is any — no restriction on upright or sideways. Touch protection is built in.

Frequently asked questions

Where can I buy 5SV9313-7CN10 and how do I get a price?

We source this RCBO to order against an RFQ. Availability and current pricing are confirmed at quote time — submit a request and we'll respond with a firm price and lead time.

What is 5SV9313-7CN10's rated current and residual trip?

It's rated 10 A with a 30 mA Type A residual-current trip, C-curve characteristic.

What breaking capacity does 5SV9313-7CN10 have?

4.5 kA per EN 60898 and 5 kA per IEC 60947-2.

MPN