Integrator note — 5SV9316-0PK06
The Siemens 5SV9316-0PK06 is a 1P+N RCD-operated circuit breaker (RCBO) from the SENTRON 5SV9 series, combining overcurrent protection and residual current detection in a single 18 mm wide module. Rated 6 A with a B tripping characteristic, it breaks fault currents up to 6 kA per both EN 60898 and IEC 60947-2 at 230/240 V AC, 50/60 Hz. The instantaneous design means no intentional delay on the RCD side — trips when leakage exceeds the threshold. Supply connects from below; touch protection is built in.
At 40 °C it derates to 5.64 A, at 45 °C to 5.46 A, at 50 °C to 5.22 A, and at 55 °C to 5.04 A.
Panel fit and compliance
Occupies one width unit (18 mm) on the DIN rail. Silicon-free construction, which matters for potting or conformal coating processes.