RCBO – combined overcurrent and residual current protection in one module
Rated 10 A at 30 °C, it derates to 9.4 A at 40 °C, 9.1 A at 45 °C, 8.7 A at 50 °C, and 8.4 A at 55 °C — the thermal curve matters when the panel runs warm.
DIN-rail footprint and installation
Width is 18 mm (1 modular width unit), depth 77 mm, height 90 mm. Installation depth 70 mm. IP20 with connected conductors in an installed distribution board. Touch protection is built in.