Residual current sensitivity is 30 mA, AC type — the standard for personnel protection in residential and commercial final circuits. Not for high-inrush loads (D-curve territory) or purely resistive circuits (B-curve).
Depth is 77 mm with 70 mm installation depth; the top or bottom supply position is flexible for panel layout. Temperature derating applies: 32 A at 30 °C ambient, 30.4 A at 40 °C, 28.8 A at 50 °C. Mounting position any, but derate per the published curve when packing multiple units in a closed enclosure.
Touch protection is integral. Compliance per IEC 81346-2 and DIN EN 61346-2 function designation F.