Skip to main content
Siemens 5SV9316-1PK32 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV9316-1PK32 SENTRON RCBO, 32 A, 30 mA, Type AC, C-

MPN5SV9316-1PK32
Active

Siemens SENTRON 5SV9316-1PK32, RCD-operated circuit breaker, 1P+N, 32 A, 30 mA, Type AC, Tripping characteristic C, 6 kA, 77x18x90 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV9316-1PK32 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV9316-1PK32 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous
5SV9316-1PK32 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SV9316-1PK32 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SV9316-1PK32 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens 5SV9316-1PK32 is a SENTRON RCBO — a combined RCD and MCB in one 18 mm wide module, protecting a single-phase final circuit against overload, short-circuit, and earth leakage.

Single modular-width unit (18 mm) snaps onto standard DIN rail. Depth is 77 mm, installation depth 70 mm — fits flush in most 80 mm deep enclosures. Supply feeds from below; any mounting position allowed. IP20 only once the distribution board is installed and conductors connected, so it's not a standalone outdoor device.

Thermal derating and environment

Rated 32 A at 30 °C, but derates to 30.4 A at 40 °C, 29.44 A at 45 °C, 28.8 A at 50 °C, and 27.84 A at 55 °C. If your panel runs warm, size the upstream breaker accordingly. Silicon-free construction matters for automotive or paint-line environments where silicone outgassing causes adhesion failures.

Frequently asked questions

How do I get current pricing and availability for 5SV9316-1PK32?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through independent distribution channels.

What is 5SV9316-1PK32's listed depth?

77 mm overall depth, with a 70 mm installation depth behind the panel face.

What is 5SV9316-1PK32's width?

18 mm — one modular width unit on standard DIN rail.

Will 5SV9316-1PK32 drop into a panel specified around 5SL4106-7CC without rewiring?

Not directly — the 5SL4106-7CC is a standard MCB without residual-current protection, while the 5SV9316-1PK32 is an RCBO. The footprint (18 mm width, DIN rail) is the same, but the wiring and circuit protection function differ. Verify the circuit's earth-leakage requirements before substituting.

MPN
5SV9316-1PK32