Skip to main content
Siemens 5SV9316-7PK06 — Residual Current Breakers (RCCB/RCBO)

Siemens SENTRON 5SV9316-7PK06 RCBO, 2P, 6A C, 30mA, 6kA

MPN5SV9316-7PK06
Active

Siemens SENTRON RCBO, 2-pole, 6 A, C-curve, 30 mA residual current, 6 kA breaking capacity per EN 60898 / IEC 60947-2, 1 MW width, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SV9316-7PK06 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV9316-7PK06 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous
5SV9316-7PK06 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SV9316-7PK06 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SV9316-7PK06 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The C-curve tripping characteristic (6 A rated at 30 °C, derated to 5.64 A at 40 °C and 5.04 A at 55 °C) handles moderate inrush from motorized loads and lighting ballasts; the 30 mA Type A residual-current element catches pulsating DC faults common in modern electronics.

Panel integration — DIN rail footprint and mounting

Width is 18 mm (one modular unit), depth 77 mm, height 90 mm. Installation depth 70 mm — the extra 7 mm is the front toggle and test button. Mounting position any; supply from below. Touch protection is built in. Silicon-free construction matters for potting or conformal-coating environments where silicone outgassing can cause contact failure.

Frequently asked questions

Who supplies 5SV9316-7PK06 and how is it quoted for volume purchases?

Available through independent distribution; sourced and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 5SV9316-7PK06?

6 kA per EN 60898 and IEC 60947-2 — sufficient for final circuits with prospective fault current under that level.

What is the temperature derating curve for this RCBO?

Rated 6 A at 30 °C, derates to 5.64 A at 40 °C, 5.46 A at 45 °C, 5.22 A at 50 °C, and 5.04 A at 55 °C.

What compliance documentation does Siemens provide for 5SV9316-7PK06?

The product carries EN 60898 and IEC 60947-2 ratings; compliance documentation (declarations of conformity, CE marking) is standard for SENTRON series RCBOs. Specific RoHS, REACH, or UL statements should be requested at quote time.

MPN
5SV9316-7PK06