The C-curve tripping characteristic (6 A rated at 30 °C, derated to 5.64 A at 40 °C and 5.04 A at 55 °C) handles moderate inrush from motorized loads and lighting ballasts; the 30 mA Type A residual-current element catches pulsating DC faults common in modern electronics.
Panel integration — DIN rail footprint and mounting
Width is 18 mm (one modular unit), depth 77 mm, height 90 mm. Installation depth 70 mm — the extra 7 mm is the front toggle and test button. Mounting position any; supply from below. Touch protection is built in. Silicon-free construction matters for potting or conformal-coating environments where silicone outgassing can cause contact failure.