Skip to main content
Siemens 5SV9316-7PK16 — Residual Current Breakers (RCCB/RCBO)

Siemens SENTRON 5SV9316-7PK16 RCBO, 2-pole, 16 A, 30 mA, Typ

MPN5SV9316-7PK16
Active

Siemens SENTRON 5SV9316-7PK16, RCBO, 2-pole, 16 A, 30 mA, Type A, 6 kA, 1 MW, IP20.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SV9316-7PK16 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SV9316-7PK16 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous

Mechanical

5SV9316-7PK16 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height90 mm
Depth77 mm
Installation depth70 mm

Environmental

5SV9316-7PK16 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Electrical

5SV9316-7PK16 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

Product identity and key ratings

The Siemens SENTRON 5SV9316-7PK16 is a 2-pole RCBO — an RCD-operated circuit breaker combining overcurrent and residual current protection in a single 18 mm wide module. It is rated 16 A at 30 °C with a 30 mA residual current trip threshold, Type A (pulsating DC and AC sensitive). The tripping characteristic is Class C, instantaneous design, meaning it trips on short-circuit without intentional delay. Breaking capacity is 6 kA per both EN 60898 and IEC 60947-2, which covers the majority of residential and light commercial distribution board fault levels. The insulation voltage (Ui) is rated 264 V, overvoltage category III, pollution degree 2 — standard for fixed-installation final circuits.

Thermal derating and ambient limits

The 16 A rating holds at 30 °C ambient. Above that, the continuous current must be derated: 15.2 A at 40 °C, 14.72 A at 45 °C, 14.24 A at 50 °C, and 13.76 A at 55 °C. The maximum operating ambient is 75 °C, minimum -40 °C. Mounting position is any, which simplifies panel layout.

DIN-rail footprint and installation

The 5SV9316-7PK16 occupies 1 modular width unit (18 mm) on a standard DIN rail. Depth is 77 mm, height 90 mm, installation depth 70 mm. The supply cord connects from below. Touch protection is provided per the product feature. IP20 rating applies when installed in a distribution board with connected conductors.

Frequently asked questions

What is the breaking capacity of 5SV9316-7PK16?

The breaking capacity is 6 kA per both EN 60898 and IEC 60947-2, which covers standard residential and light commercial distribution board fault levels.

What is the residual current type and rating?

It is Type A (sensitive to pulsating DC and AC residual currents) with a rated tripping fault current of 30 mA.

How do I get current pricing and availability for 5SV9316-7PK16?

The part is sourced to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

MPN
5SV9316-7PK16