Skip to main content
Siemens 5SY3004-7KL — 1-Pole MCB (DIN Rail)

Siemens 5SY3004-7KL SENTRON MCB, 1P+N C-curve 4A 4.5kA

MPN5SY3004-7KL

Siemens SENTRON 5SY3004-7KL, miniature circuit breaker, 1P+N, C-curve, 4 A rated, 4.5 kA breaking capacity at 230 V AC, 50/60 Hz, 1 MW width.

$69.85Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY3004-7KL — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
5SY3004-7KL — Electrical & Protection
ParameterValue
Tripping characteristic classC
Rated value (EN 60898)4.5 kA
Energy limitation class3
Overvoltage categoryIII
5SY3004-7KL — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodstandard rail
Combined terminal, topNo
Combined terminal, bottomNo
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY3004-7KL — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

Siemens SENTRON 5SY3004-7KL — C-curve MCB, 4 A, 1P+N

The Siemens 5SY3004-7KL is a SENTRON miniature circuit breaker in a 1P+N configuration — one protected pole plus a switched neutral — with a C-curve tripping characteristic rated at 4 A and a breaking capacity of 4.5 kA per EN 60898 at 230 V AC. Single-phase operation is rated up to 250 V AC. Rated current derates with ambient temperature: 4 A at 30 °C, 3.84 A at 40 °C, and 3.76 A at 45 °C — factor that into the load schedule if the panel runs warm. Depth behind the panel is 70 mm; overall depth is 76 mm.

Integration notes

The neutral conductor is switched internally — no external neutral link needed for the 1P+N configuration. The breaker is sealable, halogen-free, and silicon-free. Vibration-resistant per IEC 60068-2-6.

Frequently asked questions

What is the breaking capacity of 5SY3004-7KL?

The breaking capacity is 4.5 kA at 230 V AC per EN 60898.

Will 5SY3004-7KL drop into a panel specified for 5SY6002-7KL without rewiring?

Both are 1-module-width (18 mm) SENTRON MCBs on standard DIN rail, so the mechanical fit is the same. The 5SY6002-7KL is a different current rating and breaking capacity — verify the load and fault current requirements before substituting.

What compliance documentation does Siemens provide for 5SY3004-7KL?

The breaker is designed to EN 60898 and carries an IP20 protection class with conductors connected. The manufacturer typically provides RoHS and REACH declarations on request through the supply channel.

Where can I buy 5SY3004-7KL and get current pricing?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

MPN
5SY3004-7KL