Skip to main content
Siemens 5SY3008-7KL — 1-Pole MCB (DIN Rail)

Siemens 5SY3008-7KL SENTRON MCB, 1P+N, C8, 4.5 kA

MPN5SY3008-7KL

Siemens SENTRON miniature circuit breaker, 1P+N, C-curve 8 A, 4.5 kA per EN 60898, 230 V AC, 18 mm wide, standard rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY3008-7KL — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
5SY3008-7KL — Electrical & Protection
ParameterValue
Tripping characteristic classC
Rated value (EN 60898)4.5 kA
Overvoltage categoryIII
5SY3008-7KL — Mounting & Connection
ParameterValue
Mounting positionany
Combined terminal, topNo
Combined terminal, bottomNo
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Torque, min.17.7 lbf·in
Torque, max.22.1 lbf·in
SealableYes
5SY3008-7KL — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SY3008-7KL is a SENTRON miniature circuit breaker (MCB) with 1P+N poles, C-curve tripping characteristic, and an 8 A rated current at 230 V AC. It breaks faults up to 4.5 kA per EN 60898 — that's the standard for household and similar installations, so this part is sized for final subcircuit protection in distribution boards, not main incoming feeders. The 1P+N configuration switches both phase and neutral, with the neutral pole switching but not protecting (no overcurrent release on N).

The IP20 rating applies only with connected conductors, so the busbar and wiring must be in place to maintain the protection level. Terminal torque range is 17.7 to 22.1 lbf·in — a standard screwdriver setting for this class.

Frequently asked questions

What is 5SY3008-7KL's width and depth?

Width is 18 mm (one DIN width unit), depth is 76 mm, and installation depth behind the panel is 70 mm.

Will 5SY3008-7KL drop into a panel that was specified around 5SY6020-7KL without rewiring?

Yes — both are 1P+N, 18 mm wide, same DIN-rail footprint, same terminal torque range, and same 230 V AC rating. The only difference is the current rating (8 A vs 20 A) and breaking capacity (4.5 kA vs 6 kA). If the panel was wired for 20 A and 6 kA, dropping in an 8 A / 4.5 kA breaker may under-protect the circuit; verify the load and fault current before swapping.

How do I get current pricing and availability for 5SY3008-7KL?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time — no automated figures here, because the market moves daily.

MPN
5SY3008-7KL