It breaks faults up to 4.5 kA per EN 60898 at 230 V AC, single-phase, and switches the neutral conductor (1+N-pole). This is an active-production part — no lifecycle concerns for new builds or spares.
At 10 A rated, it holds a 10 A continuous resistive load; derate to 9.5 A at 40 °C ambient and 9.3 A at 45 °C. Pollution degree 2 covers normal indoor environments with only non-conductive contamination. The 1+N-pole design switches both line and neutral — the neutral pole is not a protective device but isolates the circuit for safe maintenance.
Snaps onto standard DIN rail — 18 mm width occupies one modular unit. The top and bottom terminals are not combined, so each conductor lands on its own clamp — no shared bus-bar slot. Touch protection is built in. Sealable for tamper-proofing in metering or access-controlled boards.
Halogen-free and silicon-free construction reduces corrosive off-gassing in a fire. Vibration resistance tested per IEC 60068-2-6. IP20 with connected conductors — not for wet locations.