Skip to main content
Siemens 5SY3013-6 — 1-Pole MCB (DIN Rail)

Siemens SENTRON 5SY3013-6 MCB, B 13 A, 1P+N, 4.5 kA

MPN5SY3013-6

Siemens SENTRON miniature circuit breaker, 5SY3013-6, B-curve 13 A, 1P+N, 4.5 kA breaking capacity at 230 V AC, 18 mm width, DIN-rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY3013-6 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
5SY3013-6 — Electrical & Protection
ParameterValue
Tripping characteristic classB
Rated value (EN 60898)4.5 kA
Overvoltage categoryIII
5SY3013-6 — Mounting & Connection
ParameterValue
Mounting positionany
Combined terminal, topNo
Combined terminal, bottomNo
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Torque, min.17.7 lbf·in
Torque, max.22.1 lbf·in
SealableYes
5SY3013-6 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens SENTRON 5SY3013-6 is a miniature circuit breaker (MCB) rated 13 A at 230 V AC with a B tripping characteristic, 1P+N pole configuration, and a 4.5 kA breaking capacity per EN 60898. The 4.5 kA breaking capacity at 230 V is the maximum prospective fault current the device can safely interrupt; it is sized for residential and light commercial distribution boards where the available fault current at the panel is known to be below that level. The 1P+N switching means the line pole is switched and protected; the neutral pole is switched only (no overcurrent protection on neutral), common for single-phase final subcircuits where the neutral is bonded at the source.

Mounts on a standard DIN rail (35 mm) and occupies 1 width unit (18 mm). Terminal torque range is specified at 17.7 to 22.1 lbf·in; the sealable cover (yes) allows the installer to lock the setting after commissioning.

Frequently asked questions

What is the breaking capacity of 5SY3013-6?

The breaking capacity per EN 60898 is 4.5 kA at 230 V AC.

What is the difference between 5SY3013-6 and 5SY6040-6?

The 5SY6040-6 is a 40 A B-curve MCB with a 6 kA breaking capacity, compared to the 13 A, 4.5 kA rating of this part. Both share the same SENTRON family, 1P+N pole configuration, 18 mm width, and DIN-rail mounting. The 5SY3013-6 will drop into a panel specified for the 5SY6040-6 without rewiring, provided the load current and available fault current are within the lower ratings.

Where can I buy 5SY3013-6?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
5SY3013-6