Skip to main content
Siemens 5SY3016-6 — 1-Pole MCB (DIN Rail)

Siemens 5SY3016-6 SENTRON MCB, B 16 A, 1P+N, 4.5 kA

MPN5SY3016-6

Siemens SENTRON 5SY3016-6 miniature circuit breaker, B-curve, 16 A rated current, 1P+N, 4.5 kA breaking capacity at 230 V AC, 18 mm width, standard rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY3016-6 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
5SY3016-6 — Electrical & Protection
ParameterValue
Tripping characteristic classB
Rated value (EN 60898)4.5 kA
Overvoltage categoryIII
5SY3016-6 — Mounting & Connection
ParameterValue
Mounting positionany
Combined terminal, topNo
Combined terminal, bottomNo
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Torque, min.24 V
SealableYes
5SY3016-6 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SY3016-6 is a SENTRON miniature circuit breaker rated 16 A with B tripping characteristic, 1P+N poles, and a 4.5 kA breaking capacity per EN 60898 at 230 V AC.

At 16 A, it protects a 3.7 kW resistive load on a 230 V single-phase line. The 4.5 kA breaking capacity is the maximum fault current it can safely interrupt under EN 60898; that's adequate for most domestic and light commercial distribution boards, but if your panel's prospective short-circuit current exceeds 4.5 kA, you need a higher-rated unit like the 6 kA variant. The 1P+N configuration switches the phase and the neutral — the neutral is not just a solid link but a switched pole, which matters for isolation during maintenance. Rated for 230 V AC single-phase operation, overvoltage category III, so it's suited for fixed-installation distribution boards downstream of the utility meter.

Mounts on standard DIN rail, any position. Screw terminals accept 0.75 to 16 mm² solid or stranded copper — that's a wide range covering 1.5 mm² lighting circuits up to 10 mm² feeders. Tightening torque is 2 to 2.5 N·m (17.7 to 22.1 lbf·in).

Frequently asked questions

What is the breaking capacity of the 5SY3016-6?

4.5 kA at 230 V AC per EN 60898. That's the rated short-circuit capacity for this 1P+N miniature circuit breaker.

Where can I buy the 5SY3016-6?

Sourced and quoted to order against an RFQ through independent distribution. Submit a request for current pricing and availability.

How does the 5SY3016-6 compare to the 5SY6020-6?

The 5SY6020-6 is the 20 A, 6 kA sibling in the same SENTRON B-curve 1P+N family. It shares the same 18 mm width, DIN-rail mount, and terminal range (0.75–16 mm²), but carries a higher continuous current and a higher breaking capacity. If your load is under 16 A and the prospective fault current stays below 4.5 kA, the 5SY3016-6 is the correct fit; the 5SY6020-6 is the upgrade path for heavier circuits or higher fault levels.

What wire sizes does the 5SY3016-6 accept?

Screw terminals accept 0.75 to 16 mm² solid or stranded copper. Tightening torque is 2 to 2.5 N·m.

MPN
5SY3016-6