Siemens SENTRON 5SY3025-7 — 25 A C-curve MCB, 1P+N, 4.5 kA
The 4.5 kA breaking capacity per EN 60898 covers residential and light commercial branch circuits where fault current stays within that threshold — typical for most 230 V distribution boards in Europe and markets following IEC 60898.
The 25 A rated current is the continuous load the breaker carries without tripping at 30 °C ambient. The 1P+N pole configuration switches the phase and disconnects the neutral — the neutral pole is not a protected pole, so it does not provide overcurrent protection on neutral, only isolation.
The 18 mm width equals one modular unit, so it fits a standard distribution board without crowding. The breaker is sealable for tamper-proofing after commissioning.