The single-module width (18 mm) and standard DIN-rail mounting let it slot into any 35 mm rail panel where space is tight — one pole per 18 mm slice, leaving room for other branch protection.
The C-curve means the magnetic trip operates at 5 to 10 times rated current — so at 32 A, the instantaneous trip threshold sits between 160 A and 320 A. The 4.5 kA breaking capacity at 230 V AC is the standard rating for final subcircuits in most residential and commercial installations per EN 60898; if your fault level upstream exceeds that, you need a current-limiting upstream device or a higher-rated breaker like the 5SY6002-7KL (6 kA). The 1P+N configuration switches both phase and neutral but only the phase is protected — the neutral pole is a switched neutral, not a protected pole. That's typical for single-phase final circuits where the neutral is solidly bonded at the distribution board. The breaker is sealable and touch-protected per IP20 with conductors connected, so it meets the basic finger-probe safety requirement inside an enclosed panel.
Environmental and compliance profile
Vibration-resistant per IEC 60068-2-6. Mechanical endurance rated at 10,000 switching cycles.