Siemens 5SY3210-6 — 2-Pole MCB (DIN Rail)

Siemens 5SY3210-6 MCB, 2-Pole B-Curve 10A, 4.5kA/6kA

MPN5SY3210-6

Siemens SENTRON 5SY3 series, miniature circuit breaker, 2-pole, B tripping characteristic, 10 A rated current, 4.5 kA (EN 60898) / 6 kA (IEC 60947-2) breaking capacity.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY3210-6 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
5SY3210-6 — Electrical
ParameterValue
Number of poles2
5SY3210-6 — Protection
ParameterValue
Tripping characteristic classB
Overvoltage categoryIII
5SY3210-6 — Mechanical
ParameterValue
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY3210-6 — Environmental
ParameterValue
Pollution degree3

Product details

Rating and application fit

Breaking capacity is 4.5 kA per EN 60898 and 6 kA per IEC 60947-2, with a DC rating of 15 kA at 72 V per IEC 60947-2 and 5 kA at 400 V AC per UL 1077 / CSA C22.2 No. 235.

Terminal position is any orientation; the breaker is sealable for lockout/tagout compliance.

Rated for AC at 400 V and DC up to 72 V. Tripping characteristic B per EN 60898. Overvoltage category III, energy limiting class 3. The part is halogen-free and silicon-free. Touch protection is integrated. Neutral conductor switching is not provided — this is a 2-pole breaker switching both phases, not a 1P+N device.

Frequently asked questions

Where can I buy the 5SY3210-6 and how is it quoted?

The 5SY3210-6 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of the 5SY3210-6?

Breaking capacity is 4.5 kA per EN 60898, 6 kA per IEC 60947-2 at 400 V AC, 15 kA DC per IEC 60947-2 at 72 V, and 5 kA per UL 1077 / CSA C22.2 No. 235.

Will the 5SY3210-6 drop into a panel specified for the 5SL3120-6MB?

The 5SY3210-6 and 5SL3120-6MB are both 2-pole DIN-rail MCBs, but the 5SY3 series has a different breaking capacity profile and tripping curve. Verify the specific ratings and coordination study before substituting — the 5SY3210-6 uses a B curve, while the 5SL series may differ.

MPN
5SY3210-6