Skip to main content
Siemens 5SY4101-6CC — 1-Pole MCB (DIN Rail)

Siemens 5SY4101-6CC SENTRON MCB, 1A, B Curve, 10kA, 1P

MPN5SY4101-6CC

Siemens SENTRON 5SY4101-6CC miniature circuit breaker, 1 A, B characteristic, 1-pole, 10 kA breaking capacity, 18 mm width.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4101-6CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SY4101-6CC — Electrical & Protection
ParameterValue
Tripping characteristic classB
Energy limitation class3
Overvoltage categoryIII
5SY4101-6CC — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY4101-6CC — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens SENTRON 5SY4101-6CC is a 1-pole miniature circuit breaker rated at 1 A with a B tripping characteristic and 10 kA breaking capacity per EN 60898.

The 18 mm width (1 MW) means you can pack up to 16 of these in a standard 300 mm enclosure row. The IP20 rating applies with conductors connected — keep the front cover closed during panel live-work. Touch protection is built into the design.

Thermal derating and environment

Rated current is 1 A at 35 °C ambient. Above that, derate: 0.94 A at 40 °C, 0.91 A at 45 °C, 0.88 A at 50 °C, and 0.84 A at 55 °C. Pollution degree 3 (conductive pollution) is covered — suitable for most control rooms and light industrial floors.

Frequently asked questions

Where can I buy 5SY4101-6CC and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability.

What is the breaking capacity of 5SY4101-6CC?

10 kA rated breaking capacity per EN 60898, sufficient for most industrial panel fault levels at 230/400 V AC.

What is the width of 5SY4101-6CC?

18 mm, which is one modular unit (1 MW) on a standard DIN rail.

MPN