Skip to main content
Siemens 5SY4101-8CC — 1-Pole MCB (DIN Rail)

Siemens 5SY4101-8CC SENTRON MCB, 1A D-Curve, 1P, 10kA

MPN5SY4101-8CC

Siemens SENTRON 5SY4101-8CC, miniature circuit breaker, 1-pole, 1 A rated, D characteristic, 10 kA per EN 60898, 440 V AC max, 1 MWU, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4101-8CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SY4101-8CC — Electrical & Protection
ParameterValue
Tripping characteristic classD
Overvoltage categoryIII
5SY4101-8CC — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY4101-8CC — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The 1 A rating holds at 35 °C ambient. Above that, the thermal-magnetic trip element derates: 0.92 A at 40 °C, 0.88 A at 45 °C, 0.83 A at 50 °C, and 0.78 A at 55 °C. If your panel runs warm — say 50 °C inside a sealed enclosure — you're actually getting an 0.83 A breaker. Size up one frame if the load is near the nominal rating.

Combined terminal top and bottom accept the same wire range. Touch protection is built in. The breaker is sealable (tamper-proof with a lead seal) and halogen-free / silicon-free — relevant for clean-room or corrosive-gas environments. Humidity limits are specified per the temperature band: max 95% RH up to 55 °C, derating to 35% at 75 °C.

Frequently asked questions

What is the breaking capacity of the 5SY4101-8CC?

10 kA rated breaking capacity per EN 60898, at 440 V AC multi-phase.

What does the D tripping characteristic mean for this MCB?

The D curve allows higher inrush currents without tripping — typically used for motor or transformer circuits where the start-up surge exceeds what a B or C curve would pass.

Where can I buy the 5SY4101-8CC and how is it quoted?

Sourced to order through independent distribution. Submit an RFQ for current availability and pricing — no stock figure or price is listed here.