Skip to main content
Siemens 5SY4102-7KK11 — 1-Pole MCB (DIN Rail)

Siemens 5SY4102-7KK11 SENTRON MCB, 1P C-curve 2A, 10kA

MPN5SY4102-7KK11

Siemens SENTRON 5SY4102-7KK11, 1-pole miniature circuit breaker, C-curve, 2 A rated at 35 °C, 10 kA per EN 60898, 35 kA per IEC 60947-2, 1 MWU, IP20.

$64.43Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4102-7KK11 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Application suitabilityMechanical engineering / industry
5SY4102-7KK11 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Rated value (EN 60898)10 kA
Energy limitation class3
Overvoltage categoryIII
5SY4102-7KK11 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY4102-7KK11 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

Siemens 5SY4102-7KK11 — SENTRON 1P C-curve 2 A MCB

Rated 2 A at 35 °C, derated to 1.9 A at 40 °C, 1.85 A at 45 °C, 1.8 A at 50 °C, 1.75 A at 55 °C, and 1.7 A at 60 °C. In a warm panel near 50 °C, you lose 10 % of the rated current — size accordingly.

Where it is used

Designed for railway applications per the product designation, and suitable for mechanical engineering and industry.

Frequently asked questions

Where can I buy 5SY4102-7KK11 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote — availability and current pricing are confirmed at quote time.

What is 5SY4102-7KK11's listed depth (76 mm) on this component line?

The depth is 76 mm. Installation depth is 70 mm, so it needs about 6 mm of clearance behind the DIN rail for wiring.

What is 5SY4102-7KK11's listed width (18 mm) on this component line?

Width is 18 mm, which is 1 modular width unit (1 MWU). It occupies one standard DIN-rail slot.

Will 5SY4102-7KK11 drop into a panel that was specified around 5SY4101-7CV without rewiring?

Both are 1-pole SENTRON MCBs with the same 18 mm width and DIN-rail mount. The 5SY4101-7CV is a different rating and curve — verify the load current and trip characteristic before swapping. The footprint and terminal arrangement are the same.

What compliance documentation does this brand provide for 5SY4102-7KK11 (RoHS, REACH, UL, IEC)?

The part is designed to EN 60898 and IEC 60947-2. It is halogen-free and silicon-free. For specific RoHS/REACH/UL declarations, request the manufacturer's compliance documentation at quote time.

MPN