Siemens 5SY4102-7KK11 — SENTRON 1P C-curve 2 A MCB
Rated 2 A at 35 °C, derated to 1.9 A at 40 °C, 1.85 A at 45 °C, 1.8 A at 50 °C, 1.75 A at 55 °C, and 1.7 A at 60 °C. In a warm panel near 50 °C, you lose 10 % of the rated current — size accordingly.
Where it is used
Designed for railway applications per the product designation, and suitable for mechanical engineering and industry.