It clears faults at 10 kA per EN 60898 and 35 kA per IEC 60947-2, with a UL 1077 / CSA C22.2 No. 235 interrupting capacity of 5 kA. The single-pole format (1P) fits a 27 mm wide module on a DIN rail, one width unit per EN 60715.
Sizing and selectivity for the panel builder
The 5SY4103-7XX02 accepts conductors from 0.75 mm² up to 35 mm² solid or stranded, with a tightening torque of 2.5–3.5 N·m on the screw terminals. That wire range covers everything from 1.5 mm² final subcircuits up to 10 mm² incoming tails — useful when the MCB is the first device after a meter or sub-distribution board.
Rated for AC only (type of voltage: AC) with a maximum DC voltage of 72 V. The product carries approvals per EN 60898, IEC 60947-2, and UL 1077 / CSA C22.2 No. 235 — covering European, international, and North American acceptance. Sealable for tamper-proof installations.