Siemens 5SY4104-7CC11 — 1-Pole MCB (DIN Rail)

Siemens 5SY4104-7CC11 SENTRON MCB, 4A, 1P, C-Curve, 10kA

MPN5SY4104-7CC11

Siemens SENTRON 5SY4104-7CC11 miniature circuit breaker, 1-pole, 4 A rated current, C tripping characteristic, 10 kA breaking capacity per EN 60898, 18 mm width, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4104-7CC11 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SY4104-7CC11 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Rated value (EN 60898)10 kA
Energy limitation class3
Overvoltage categoryIII
5SY4104-7CC11 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY4104-7CC11 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

Siemens 5SY4104-7CC11 SENTRON MCB — 4 A, 1-Pole, C-Curve

It is designed for branch-circuit protection in industrial control panels, distribution boards, and railway auxiliary systems — the product designation explicitly states its suitability for railway applications. Mounting position is unrestricted, so it can be installed horizontally or vertically without derating.

The 4 A rating holds at 35 °C. Above that, the continuous current must be derated: 3.76 A at 40 °C, 3.64 A at 45 °C, 3.5 A at 50 °C, 3.37 A at 55 °C, and 3.23 A at 60 °C (–). If the panel ambient runs at 50 °C, the effective capacity drops to 3.5 A — factor that into your load calculation rather than relying on the 35 °C nameplate figure. Humidity limits are specified: max 95% up to 55 °C, then 55% up to 70 °C, and 35% up to 75 °C — relevant if the breaker sits in a washdown area or coastal installation.

Construction and Environmental Compliance

The 5SY4104-7CC11 is halogen-free and silicon-free — important for applications where outgassing from a fault could corrode nearby contacts or optics, such as in clean rooms, medical equipment, or sealed enclosures. Overvoltage category III suits fixed installations and distribution boards. The breaker is sealable — a feature for applications where tamper-evident sealing is required after commissioning.

Frequently asked questions

What is the breaking capacity of 5SY4104-7CC11?

The breaking capacity is 10 kA per EN 60898, suitable for most industrial and commercial sub-distribution fault levels.

What is the rated current of 5SY4104-7CC11 at elevated ambient temperatures?

Rated current is 4 A at 35 °C. At 40 °C it derates to 3.76 A, at 50 °C to 3.5 A, and at 60 °C to 3.23 A (–).

Where can I buy 5SY4104-7CC11 and how is it quoted?

The part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the tripping characteristic of 5SY4104-7CC11?

It has a C tripping characteristic, meaning it trips between 5 and 10 times rated current — designed for moderate inrush loads like small motors, contactors, and control transformers.