Siemens 5SY4104-7XX02 — 1-Pole MCB (DIN Rail)

Siemens 5SY4104-7XX02 SENTRON MCB, 1P C-curve, 10kA IEC 6089

MPN5SY4104-7XX02

Siemens SENTRON 5SY4104-7XX02, 1-pole miniature circuit breaker, C-curve, 10 kA breaking capacity per IEC/EN 60898-1, 35 kA per IEC 60947-2, with integrated auxiliary switch 1NO+1NC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4104-7XX02 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SY4104-7XX02 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Energy limitation class3
Overvoltage categoryIII
5SY4104-7XX02 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width27 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY4104-7XX02 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The integrated auxiliary switch (1NO+1NC) provides remote status feedback without requiring a separate add-on module — a space-saving detail for panels where every DIN rail millimeter counts.

The dual breaking-capacity rating is the key specification for this MCB. For comparison, a sibling like the 5SY4101-7CV carries the same dual ratings but with a B-curve trip characteristic, which trips faster on lower overcurrents and is better suited for resistive loads or long cable runs where nuisance tripping from inrush is a concern. The C-curve on this 5SY4104-7XX02 is the standard choice for motor branch circuits and mixed loads.

Snap-on DIN rail mounting, any position. Width is 1 modular unit (27 mm), installation depth 70 mm, overall depth 76 mm.

It also carries a UL 1077 / CSA C22.2 No. 235 rating of 5 kA for North American acceptance. Halogen-free and silicon-free construction. Energy limitation class 3, overvoltage category III, vibration resistance per IEC 60068-2-6. The sealable design allows lockout/tagout for maintenance safety.

Frequently asked questions

Where can I buy the 5SY4104-7XX02 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the difference between the 5SY4104-7XX02 and the 5SY4104-7CV?

The -7XX02 has combined top and bottom terminals (screw + clamp), while the -7CV uses screw terminals only. Both are 1-pole C-curve MCBs with the same breaking capacities, auxiliary switch, and DIN-rail footprint — they are form-fit-function interchangeable in the panel.

What breaking capacity does the 5SY4104-7XX02 have?

It is dual-rated: 10 kA per IEC/EN 60898-1 and 35 kA per IEC 60947-2 at 400 V AC. For UL/CSA applications, it carries a 5 kA rating per UL 1077 and CSA C22.2 No. 235.

What compliance documentation is available for the 5SY4104-7XX02?

The MCB is designed to IEC/EN 60898-1 and IEC 60947-2, with UL 1077 and CSA C22.2 No. 235 ratings. It is halogen-free and silicon-free. Standard documentation includes the datasheet, CE declaration, and REACH/RoHS compliance statements available on request.

MPN