It's rated 10 kA per IEC / EN 60898-1 and 35 kA per IEC 60947-2 — the 35 kA figure is what you use for industrial panel SCCR coordination, not the residential-grade 10 kA. At DC it breaks 15 kA at 60 V (72 V max) per IEC 60947-2, and 5 kA per UL 1077 / CSA C22.2 No. 235 for North American installations.
Depth is 76 mm (70 mm installation depth), which means it clears most standard enclosures without a deep-can. The combined terminal on top and bottom accepts copper conductors; sealable with a lead seal for tamper-proofing.
Ambient temperature range runs -40 °C to 75 °C, with humidity derating above 55 °C (95% RH up to 55 °C, 55% at 70 °C, 35% at 75 °C). Vibration resistance per IEC 60068-2-6: ±1 mm at 5 to 25 Hz, 50 m/s² at 25 to 150 Hz — holds up on a machine tool or conveyor line without nuisance trips. Halogen-free and silicon-free construction for clean-room or sensitive electronics environments.